Description

The GW4-40.5/126 Disconnect Switch is a newly developed model based on our original series, designed to meet the enhanced technical requirements of the State Grid Corporation. It is suitable for outdoor power distribution systems with a rated voltage of 40.5/126 kV, three-phase AC, 50 Hz.

The switch is used to open and close power lines and equipment under voltage but without load, providing reliable electrical isolation. The product consists of three independent poles, each built with a double-column portal structure and composed of a base, insulator posts, and conductive components.

Each pole features two insulator columns mounted on bearing seats connected to the base. The opening and closing operations are driven by a four-link mechanism. The switch can be equipped with single-side or double-side earthing switches, available in four configurations: non-earthing, left earthing, right earthing, and double earthing.

Product Features

External-compression contact spring
Prevents current-carrying failure due to spring degradation, effectively reducing operational risks.

High-strength conductive structure
Conductive tubes are made of square aluminum alloy; flexible connectors use copper. All contact surfaces are silver-plated for excellent conductivity and mechanical strength.

Reliable transmission system
The operating mechanism uses stainless steel pins and composite bushings, ensuring low friction and stable transmission performance.

Safety interlock
A dependable interlocking device is installed between the main blade and the earthing blade to prevent incorrect operation.

Fully sealed base design
Prevents water and dust intrusion. The bearing seat includes an oil injection port, enabling maintenance without power outage, enhancing reliability and convenience.

Strong anti-corrosion protection
Major steel components are hot-dip galvanized, providing excellent appearance quality and superior corrosion resistance.

Technical Parameters
No. Item Unit Technical Data
1 Rated Voltage kV 40.5 126
2 Rated Frequency Hz 50
3 Rated Current A 1250 2000 2500 4000
4 Main Circuit Resistance μΩ ≤200 ≤150 ≤100 ≤85
5 Temperature Rise Test Current A 1.1 × Rated Current
6 Rated Power Frequency Withstand Voltage (1 min) To Earth kV 95 230
Across Gap 118 230+70
Rated Lightning Impulse Withstand Voltage (1.2/50ms) Peak To Earth kV 185 550
Across Gap 215 550+100
7 Rated Short-time Withstand Current and Duration Disconnector kA/s 25/4 31.5/4 40/4 40/4
Earthing Switch 25/4 31.5/4 40/4 40/4
8 Rated Peak Withstand Current kA 63 80 100 100
9 Bus-transfer Current Switching Capability Transfer Current A 1600
Transfer Voltage V 100
Breaking Operations Times C-O 100 times
10 Capacitive Current Switching A 1
11 Inductive Current Switching A 0.5
12 Earthing Switch Induced Current Switching Capability Electromagnetic Induction Inductive Current A 50
Recovery Voltage kV 0.5
Breaking Operations Times O, C 10 times each
Electrostatic Induction Capacitive Current A 0.4
Recovery Voltage kV 3
Breaking Operations Times O, C 10 times each
13 Mechanical Endurance Times 3000
14 Aux. & Control Circuit Short-time Power Freq. Withstand Voltage kV 2
15 Terminal Static Mechanical Load Horizontal Longitudinal N 800 1000,1250
Horizontal Transverse 500 750
Vertical 750 1000
16 Post Insulator Creepage Distance mm ≥1256 ≥3906
Post Height 550 1200
Reviews (0)

Reviews

There are no reviews yet.

Be the first to review “GW4-40.5/126 Outdoor High-Voltage AC Disconnect Switch”

Your email address will not be published. Required fields are marked *

Shipping and Delivery

MAECENAS IACULIS

Vestibulum curae torquent diam diam commodo parturient penatibus nunc dui adipiscing convallis bulum parturient suspendisse parturient a.Parturient in parturient scelerisque nibh lectus quam a natoque adipiscing a vestibulum hendrerit et pharetra fames nunc natoque dui.

ADIPISCING CONVALLIS BULUM

  • Vestibulum penatibus nunc dui adipiscing convallis bulum parturient suspendisse.
  • Abitur parturient praesent lectus quam a natoque adipiscing a vestibulum hendre.
  • Diam parturient dictumst parturient scelerisque nibh lectus.

Scelerisque adipiscing bibendum sem vestibulum et in a a a purus lectus faucibus lobortis tincidunt purus lectus nisl class eros.Condimentum a et ullamcorper dictumst mus et tristique elementum nam inceptos hac parturient scelerisque vestibulum amet elit ut volutpat.